CODE A+
Severity: High
Difficulty: Advanced
Address Overflow Capacity Fault
Error code A+ indicates an indoor unit addressing allocation overflow or capacity mismatch on the TCL DM4 VRF outdoor master board. The main outdoor microcontroller (MCU) triggers this lockout when detected indoor units exceed address registry limits, duplicate addresses exist, or total indoor capacity exceeds 130% of rated outdoor tonnage.
⏱ 30-45 Mins